Fast master debut to integrated controller.
It is possible to connect directly with the MICREX-SX series.

Master interface specification for NP1L-AW1 MICREX-SX

Correspondence CPU unit SPH200,SPH300,SPH2000
I/O number 4 all pile mode: 2560 or less Point
(Bit-Bus: 512 points or less/Word-Bus: 2048 or less point)
AnyWireBus port One port and detachable terminal stand
Connected the number 128 or less
Transmission distance The total extension 100m, 200m, 500m, and 1km are selected.
Transmission cycle time Unit[msec] (one cycle time value)
Four-all pile mode bit bus 62.5kHz 31.3kHz 15.6Hz 7.8kHz
64 points 0.85 1.7 3.4 6.8
128 points 1.4 2.7 5.4 10.9
256 points 2.4 4.8 9.5 19.1
512 points 4.4 8.9 17.7 35.5
Four-all pile mode word bus 62.5kHz 31.3kHz 15.6Hz 7.8kHz
IN8word/OUT8word 2.5 5.0 9.9 19.8
IN16word/OUT16word 4.7 9.3 18.6 37.2
IN32word/OUT32word 9.0 18.0 36.0 72.1
IN64word/OUT64word 17.7 35.4 70.9 141.7
RAS function Transmission line disconnection position detection function, transmission line short-circuit detection function, and transmission power supply decrease detection function
Connecting cable Two general-purpose wicks/four wick cable (VCTF 0.75-1.25sq)
Special flat cable (0.75sq) and general-purpose electric wire(0.75~1.25sq)
Power supply Internal power dissipation DC24V 100mA or less (supply from SX bus side)
DC24V+15–10% ripple 0.5Vp-p or less
About 0.2A or less in current(When 128 in the terminal is connected, the load current is not included. )
Ambient temperature of use 0℃~+55 ℃ (:-25-+70℃ in preservation temperature)
Use humidity 20~95%%RH (dewfall)
Atmosphere he causticity gas, the flammable gas, and an organic solvent doesn’t adhere.