EVS SERIES, EVS-RP
Model name
Features
- Trimmers on power supply allow presetting of charge current and charge voltage to implement constant current constant voltage charging
- 300 W model features fanless design
- Various output voltage ratings to match storage system voltages are available
- Compliant with UL 60950-1 and EN60950-1 safety standards
- Developed the backflow prevention module
For 12 V storage systems: 18 V output type * Only available as 300 W model
For 24 V storage systems: 36 V output type
For 48 V storage systems: 57 V output type
Model:EVS-RP6020
Low loss: Due to using MOS-FET, 72% reduction of forward voltage comparing with schottky-barrier diode.
(Input:7~60VDC, 20Amax, Reverse current:50μAmax
Inside loss:4Wmax, Convection cooling, Size:50x26x77.5)
Specifications
Model | EVS18-16R7 | EVS36-8R4 | EVS57-5R3 | EVS36-16R7 | EVS57-10R6 |
---|---|---|---|---|---|
Input Voltage Range | 85~265VAC / 120~370VDC | 85~265VAC / 120~330VDC | |||
Constant Voltage ModeRated Voltage(Adjustable range) | 18VDC(12~18VDC) | 36VDC(24~36VDC) | 57VDC(48~57VDC) | 36VDC(24~36VDC) | 57VDC(48~57VDC) |
Constant Current ModeRated Current100 VAC(200 VAC) | 16.7A(16.7A) | 8.4A(8.4A) | 5.3A(5.3A) | 15.3A(16.7A) | 9.7A(10.6A) |
Rated CurrentAdjustable Range100 VAC(200 V AC) | 8.35~16.7A(8.35~16.7A) | 4.2~8.4A(4.2~8.4A) | 2.65~5.3A(2.65~5.3A) | 8.35~15.3A(8.35~16.7A) | 5.3~9.7A(5.3~10.6A) |
Maximum Output Power | 300W | 600W | |||
Remote ON/OFF Control | Option (/R) | ||||
Parallel/Series Operation | Possible | ||||
Safety | UL60950-1, EN60950-1 | ||||
Cooling | Convection cooling | Forced air by blower fan | |||
Outline | PC Board Type | Unit Type | |||
Dimension(WxHxD)mm | 84 x 42 x 180 | 120 x 61 x 190 |