ANYWIRE DB Master Unit - AFCS01 | TKK Corporation


Anywire DB Master Unit – AFCS01

SYSMAC™ Fast master debut to PLC.
SYSMAC™ It is possible to connect directly with the CS1 series.

AFCS01 SYSMAC™ CS1 series master interface specification

Correspondence CPU unit AFCS01
Shape CJ1G-CPU44H, shape CJ1G-CPU43H, and shape CJ1G-CPU42H
Shape CJ1G-CPU45 and shape CJ1G-CPU44
I/O number 4 all pile mode: 2560 or less Point
(Bit-Bus: 512 points or less/Word-Bus: 2048 or less point)
AnyWireBus port One port and detachable terminal stand
Connected the number 128 or less
Transmission distance The total extension 100m, 200m, 500m, and 1km are selected.
Transmission cycle time Unit[msec] (one cycle time value)
Four-all pile mode bit bus 62.5Khz 31.3Khz 15.6Hz 7.8Khz
64 points 0.85 1.7 3.4 6.8
128 points 1.4 2.7 5.4 10.9
256 points 2.4 4.8 9.5 19.1
512 points 4.4 8.9 17.7 35.5
Four-all pile mode word bus 62.5kHz 31.3kHz 15.6Hz 7.8kHz
IN8word/OUT8word 2.5 5.0 9.9 19.8
IN16word/OUT16word 4.7 9.3 18.6 37.2
IN32word/OUT32word 9.0 18.0 36.0 72.1
IN64word/OUT64word 17.7 35.4 70.9 141.7
RAS function Transmission line disconnection position detection function, transmission line short-circuit detection function, and transmission power supply decrease detection function
Connecting cable Two general-purpose wicks/4 Wick cable (VCTF 0.75-1.25sq)
Special flat cable (0.75sq) and general-purpose electric wire(0.75~1.25sq)
Power supply +5V±5% 0.4A (supply from CS1 side)
DC24V +15%-10% ripple 0.5Vp-p or less
About 0.2A or less in current(When 128 in the terminal is connected, the load current is not included. )
Ambient temperature of use 0℃~+55 ℃ (preservation temperature :- 20℃-+75℃)
Use humidity 10%~90%RH (dewfall)
Atmosphere Causticity gas and flammable gas