ANYWIRE DB Master Unit - AFSR01 | TKK Corporation


Anywire DB Master Unit- AFSR01

Fast master debut to micro PLC.
FA-M3 It is possible to connect directly with the series.

AFSR01 FA-M3™ series master interface specification

Correspondence CPU unit F3SP21-0N,F3SP25-2N,F3SP28-3N,F3SP35-5N,F3SP38-6N,F3SP53-4H,F3SP58-6H,F3FP36-3N,F3SP28-3S,F3SP38-6S,F3SP53-4S,F3SP58-6S,F3SP59-7S
I/O number 4 all pile mode: 2560 or less Point
(Bit-Bus: 512 points or less/Word-Bus: 2048 or less point)
AnyWireBus port One port and detachable terminal stand
Connected the number 128 or less
Transmission distance The total extension 200m, 500m, and 1km are selected.
Transmission cycle time Unit[msec] (one cycle time value)
4 all Pile mode bit bus 62.5kHz 31.3kHz 15.6Hz 7.8kHz
64 points 0.85 1.7 3.4 6.8
128 points 1.4 2.7 5.4 10.9
256 points 2.4 4.8 9.5 19.1
512 points 4.4 8.9 17.7 35.5
Four-all pile mode word bus 62.5kHz 31.3kHz 15.6Hz 7.8kHz
IN8word/OUT8word 2.5 5.0 9.9 19.8
IN16word/OUT16word 4.7 9.3 18.6 37.2
IN32word/OUT32word 9.0 18.0 36.0 72.1
IN64word/OUT64word 17.7 35.4 70.9 141.7
RAS function Transmission line disconnection position detection function, transmission line short-circuit detection function, and transmission power supply decrease detection function
Connecting cable Two general-purpose wicks/4 Wick cable (VCTF 0.75-1.25sq) Special flat cable (0.75sq) and general-purpose electric wire(0.75~1.25sq)
Power supply +5V±5% 0.2A (supply from FA-M3 side)
+24V +15%-10% ripple 0.5Vp-p or less
Current about 0.2A Max. (When 128 in the terminal is connected, the load current is not included. )
Ambient temperature of use 0℃~+55 ℃ (preservation temperature :- 20℃-+75℃)
Use humidity 10%~90%RH (dewfall)
Atmosphere Causticity gas and flammable gas