OHM Lateral mounting type (Standard) OCA-1000BC-100V
Features
- Temperature indication
- High temperature alarm output
- Ease of maintenance
- Mountable either on the outer wall or being recessed as the space demands
Specifications
Model | OCA-1000BC-100V |
---|---|
Type of mounting | Lateral mounting |
Cooling capacity ※1 | 750/900W |
Rated voltage | Single phase 100VAC±10% |
Current consumption ※2 Rated | 8.0/7.8A or less |
Current consumption ※2 Max. | 10.8/10.7A |
Starting current | 24.2/22.3A |
Power consumption ※2 Rated | 820/800W |
Power consumption ※2 Max. | 1150/1100W |
Refrigerant | R407C (410g) |
Working temperature ※3 | +20 to +50℃ |
Temperature setting range ※3 | +30 to +45℃ (Initial setting: +35℃) |
External output | Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Display | Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function | Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder, Forced cooling operation for inspection |
Noise (Characteristic A) | 65dB |
Protective category | Internal circuit : equivalent to IP54 |
Safety/Environmental standard | PSE/RoHS |
Body color | Beige(5Y7/1 corresponding) |
Dimensions (in mm) | W350×H900×D200 |
Weight | 33.0kg |
Rated frequency (50/60Hz)
※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.
For more details and information, please visit this www.ohm.jp