OCA-2200BC-200V-R | TKK Corporation


OHM Lateral mounting type (Bottom flow) OCA-2200BC-200V-R

OHM Lateral mounting type

Features

  • Temperature indication
  • High temperature alarm output

    Ease of maintenance

    Mountable either on the outer wall or being recessed as the space demands

Specifications

Model OCA-2200BC-200V-R
Type of mounting Lateral mounting
Cooling capacity ※1 1880/2070W
Rated voltage Single phase 200VAC±10%
Current consumption ※2 Rated 3.5/3.7A or less
Current consumption ※2 Max. 4.3/4.5A
Starting current 16.0/14.0A
Power consumption ※2 Rated 1050/1150W
Power consumption ※2 Max. 1300/1420W
Refrigerant R407C (700g)
Working temperature ※3 +20 to+50℃
Temperature setting range ※3 +30 to +45℃ (Initial setting: +35℃)
External output Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load)
Display Internal temperature, Alarm code/Operation lamp, Alarm lamp
Function Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection,
Maintenance reminder, Forced cooling operation for inspection
Noise (Characteristic A) 69dB
Protective category Internal circuit : equivalent to IP54
Safety/Environmental standard PSE/RoHS
Body color Beige(5Y7/1 corresponding)
Dimensions (in mm) W450×H1150×D220
Weight 52.0kg

Rated frequency (50/60Hz)

※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.