OCA-1000BC-200V-R | TKK Corporation


OHM Lateral mounting type (Bottom flow) OCA-1000BC-200V-R

OHM Lateral mounting type

Features

  • Temperature indication
  • High temperature alarm output
  • Ease of maintenance
  • Mountable either on the outer wall or being recessed as the space demands

Specifications

Model OCA-1000BC-200V-R
Type of mounting Lateral mounting
Cooling capacity ※1 720/920W
Rated voltage Single phase 200VAC±10%
Current consumption ※2 Rated 3.1/3.3A or less
Current consumption ※2 Max. 4.2/4.3A
Starting current 13.7/12.9A
Power consumption ※2 Rated 580/670W
Power consumption ※2 Max. 730/840W
Refrigerant R407C (465g)
Working temperature ※3 +20 to+50℃
Temperature setting range ※3 +30 to +50℃ (Initial setting: +35℃)
External output Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load)
Display Internal temperature, Alarm code/Operation lamp, Alarm lamp
Function Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection,
Maintenance reminder, Forced cooling operation for inspection
Noise (Characteristic A) 65dB
Protective category Internal circuit : equivalent to IP54
Safety/Environmental standard PSE/RoHS
Body color Beige(5Y7/1 corresponding)
Dimensions (in mm) W350×H900×D200
Weight 33.0kg

Rated frequency (50/60Hz)

※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.