OCA-300AC-100V | TKK Corporation


OHM Roof mounting type OCA-300AC-100V

OHM Roof mounting type

Features

  • Safety design
  • Temperature controller equipped as standard
  • Ease of maintenance

Specifications

Model OCA-300AC-100V
Type of mounting Roof mounting
Cooling capacity ※1 300/350W
Rated voltage Single phase 100VAC±10%
Current consumption ※2 Rated 3.0/2.8A or less
Current consumption ※2 Max. 3.7/3.4A
Starting current 7.5/7.2A
Power consumption ※2 Rated 280/275W
Power consumption ※2 Max. 355/345W
Refrigerant R134a (135g)
Working temperature ※3 +20 to +50℃
Temperature setting range ※3 +30 to +45℃ (Initial setting: +35℃)
External output Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load)
Display Internal temperature, Alarm code/Operation lamp, Alarm lamp
Function Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection, Maintenance reminder,
Forced cooling operation for inspection, Detection of drain overflows
Noise (Characteristic A) 65dB
Protective category Internal circuit : equivalent to IP54
Safety/Environmental standard PSE/RoHS
Body color Beige(5Y7/1 corresponding)
Dimensions (in mm) W450×H230×D250
Weight 16.0kg

Rated frequency (50/60Hz)

※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.

For more details and information, please visit this www.ohm.jp