OCA-3000AC-200V | TKK Corporation


OHM Roof mounting type OCA-3000AC-200V

OHM Roof mounting type

Features

  • Safety design
  • Temperature controller equipped as standard
  • Ease of maintenance

Specifications

Model OCA-3000AC-200V OCA-3000AC-200V-CE
Type of mounting Roof mounting
Cooling capacity ※1 2700/3000W
Rated voltage Three phase 200VAC±10%
Current consumption ※2 Rated 4.8/5.1A or less
Current consumption ※2 Max. 5.8/6.2A
Starting current 20.0/19.0A
Power consumption ※2 Rated 1470/1620W
Power consumption ※2 Max. 1790/1980W
Refrigerant R407C (900g)
Working temperature ※3 +20 to +50℃
Temperature setting range ※3 +30 to +45℃ (Initial setting: +35℃)
External output Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load)
Display Internal temperature, Alarm code/Operation lamp, Alarm lamp
Function Off-temperature alarm, Detection of abnormal heat dissipation,
Detection of temperature sensor disconnection, Maintenance reminder,
Forced cooling operation for inspection, Detection of drain overflows
Noise (Characteristic A) 68dB
Protective category Internal circuit : equivalent to IP54
Safety/Environmental standard PSE/RoHS CE, PSE/RoHS
Body color Beige(5Y7/1 corresponding)
Dimensions (in mm) W760×H447×D400
Weight 57.0kg

Rated frequency (50/60Hz)

※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.

For more details and information, please visit this www.ohm.jp