OHM Roof mounting type OCA-300AC-100V

Features
- Safety design
- Temperature controller equipped as standard
- Ease of maintenance
Specifications
Model | OCA-300AC-100V |
---|---|
Type of mounting | Roof mounting |
Cooling capacity ※1 | 300/350W |
Rated voltage | Single phase 100VAC±10% |
Current consumption ※2 Rated | 3.0/2.8A or less |
Current consumption ※2 Max. | 3.7/3.4A |
Starting current | 7.5/7.2A |
Power consumption ※2 Rated | 280/275W |
Power consumption ※2 Max. | 355/345W |
Refrigerant | R134a (135g) |
Working temperature ※3 | +20 to +50℃ |
Temperature setting range ※3 | +30 to +45℃ (Initial setting: +35℃) |
External output | Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Display | Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function | Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder, Forced cooling operation for inspection, Detection of drain overflows |
Noise (Characteristic A) | 65dB |
Protective category | Internal circuit : equivalent to IP54 |
Safety/Environmental standard | PSE/RoHS |
Body color | Beige(5Y7/1 corresponding) |
Dimensions (in mm) | W450×H230×D250 |
Weight | 16.0kg |
Rated frequency (50/60Hz)
※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.
For more details and information, please visit this www.ohm.jp