OHM Lateral mounting type (Condensate-free) OCA-700BCD-200V
Features
- No electric power required to evaporate condensate water!!
- Innovative three-step evaporation method by means of a pan (1st) and
a fin (2nd) and a supplimentary filter (3rd) - Achieved high efficiency with less energy making use of cool condensate water to cool down the radiation fin
- Temperature indication
- High temperature alarm output
- Ease of maintenance
Specifications
Model | OCA-700BCD-200V |
---|---|
Type of mounting | Lateral mounting |
Cooling capacity ※1 | 600/700W |
Rated voltage | Single phase 200VAC±10% |
Current consumption ※2 Rated | 2.2/2.1A or less |
Current consumption During condensate evaporation ※3 | 2.1/2.0A or less |
Current consumption ※2 Max. | 2.6/2.5A |
Starting current | 9.1/8.4A |
Power consumption ※2 Rated | 390/440W |
Power consumption ※2 During condensate evaporation ※3 | 380/430W |
Power consumption ※2 Max. | 460/500W |
COP ※4 | 1.59 |
Refrigerant | R407C (280g) |
Working temperature ※5 | +20 to+50℃ |
Working humidity | 80%RH or less, Free from condensation |
Temperature setting range ※5 | +30 to +45℃ (Initial setting: +35℃) |
External output | Alarm output (no voltage c contact: 250VAC/30VDC 3A resistance load) |
Temperature and humidity conditions for evaporation | +35℃ 85%RH or less |
Display | Internal temperature, Alarm code/Operation lamp, Alarm lamp |
Function | Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder, Forced cooling operation for inspection |
Noise (Characteristic A) | 64dB |
Protective category | Internal circuit : equivalent to IP54 |
Safety/Environmental standard | PSE/RoHS |
Body color | Beige(5Y7/1 corresponding) |
Dimensions (in mm) | W350×H600×D200 |
Weight | 22.0kg |
Rated frequency (50/60Hz)
※1. CNominal value when temperatures both inside and outside the control panel are 35℃
※2. Values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max.”.
※3. Use only within the specified temperature range.
※4. COP (coefficient of performance) is the ratio of the cooling output to power consumption.
※5. Use only within the specified temperature range.